Wire Size Calculator

Enter amps, volts and the one-way distance. The calculator picks the smallest copper or aluminum wire that keeps the voltage drop within your target and carries the current under NEC Table 310.16 and 240.4(D), and tells you which of the two set the size.

Smallest wire for your circuit

System
Length unit
Conductor
Insulation / terminal rating

Use 60 °C for NM-B/UF-B cable and for circuits 100 A or less unless the breaker and equipment are marked 75 °C.

Enter amps, volts and length

Uses the K method: K = 12.9 for copper and 21.2 for aluminum (ohm-circular mils per foot at about 75 °C, consistent with NEC Chapter 9 Table 8). Ampacity per NEC Table 310.16 (2017–2023 values; 30 °C ambient, no more than three current-carrying conductors, no correction or adjustment). The 3 % / 5 % figures come from NEC informational notes and are not requirements, but local codes may make them mandatory. AC results ignore reactance and power factor, which matters most on wire larger than 1/0. For PV circuits, enter the NEC 690.8 current. Not an engineering calculation — check with your local code and inspector. NEC® and National Electrical Code® are registered trademarks of NFPA; this site is not affiliated with NFPA.

How the wire size is chosen

Two checks run side by side. The first finds the smallest wire whose voltage drop is within the target, 3 % by default. The second finds the smallest wire whose ampacity, and the 240.4(D) limit for 14, 12 and 10 AWG, is at least the load current. The recommended size is the larger of the two.

Example: 30 A at 240 V, single-phase, 150 ft one way, copper, 75 °C. 10 AWG carries 30 A, but drops 4.66 %. The calculator recommends 8 AWG: 7.03 V (2.93 %). Voltage drop sets the size.

60 °C or 75 °C

Use the 60 °C column for NM-B and UF-B cable (334.80, 340.80) and for circuits of 100 A or less, unless the breaker and the equipment terminals are marked 75 °C (110.14(C)(1)(a)). Above 100 A the 75 °C column usually applies. The calculator starts at 60 °C for 100 A or less and 75 °C above; change it if your terminals allow.

Ampacity from NEC Table 310.16 (30 °C ambient, up to three current-carrying conductors).
SizeCopper 60 °CCopper 75 °CAluminum 60 °CAluminum 75 °C
14 AWG15 A20 A——
12 AWG20 A25 A15 A20 A
10 AWG30 A35 A25 A30 A
8 AWG40 A50 A35 A40 A
6 AWG55 A65 A40 A50 A
4 AWG70 A85 A55 A65 A
2 AWG95 A115 A75 A90 A
1/0 AWG125 A150 A100 A120 A

Continuous loads

A load that runs for 3 hours or more is continuous, and the wire must carry 125 % of its current (210.19(A)(1), 215.2(A)(1)). EV chargers count as continuous loads. Tick "Continuous load" and the calculator sizes for 125 % on the ampacity side; the voltage drop still uses the actual current. A 40 A continuous load at 60 °C needs a wire rated 50 A: 6 AWG. For PV circuits, enter the current from NEC 690.8.

Copper vs aluminum

Aluminum has a higher resistance and a lower ampacity, so it needs a larger size for the same run. K = 12.9 for copper and 21.2 for aluminum (ohm-circular mils per foot at about 75 °C, consistent with NEC Chapter 9 Table 8). For the 30 A, 150 ft example, aluminum needs 4 AWG instead of 8 AWG copper. Aluminum is common for feeders and service conductors in 1/0 and larger. Use terminals rated for aluminum.

Check a wire you already picked

Questions

What size wire do I need for 30 amps at 150 feet?

At 240 V single-phase with copper and a 3 % target, 8 AWG: it drops 2.93 %. At 120 V the drop doubles in percent, so you need 4 AWG. Enter your own numbers above.

How do I size wire for voltage drop?

Pick the smallest wire whose voltage drop, 2 × K × I × L ÷ CM, stays within your target, then check that its ampacity carries the current. The calculator does both and tells you which one set the size.

What is the difference between 60 °C and 75 °C ampacity?

They are columns of NEC Table 310.16 for different insulation and terminal ratings. 6 AWG copper is rated 55 A at 60 °C and 65 A at 75 °C. You can only use the 75 °C column when the wire, the breaker and the equipment are all rated for it.

Can I use aluminum wire?

Yes, where the code and the equipment allow it, with terminals rated for aluminum. It needs a larger size than copper: for 30 A at 240 V over 150 ft, 4 AWG aluminum instead of 8 AWG copper.